This manual also contains all user-pertinent specifications and semiconductor fusing recommendations. Refer to national and local electrical code safety guidelines whenever you install electrical equipment. The Watlow DIN-A-MITE power controller includes single-phase, 3-phase, 2-leg, and 3. DIN-A-MITE C. The DIN-A-MITE C silicon controlled rectifier (SCR) power controller provides a low cost, compact and versatile solid state controller option for controlling electric heat. This solid state controller is designed and manufactured with the quality features expected from Watlow.
2
The Watlow DIN-A-MITE A Series Power-Switching Device Controller is capable of single-phase zero-cross switching up to 25 amperes at 600VAC. A unique integrated design removes the guesswork associated with selecting a proper heat sink and adequate terminations for the application. The DIN-A-MITE is also mercury free. Control Console User's Manual, Rev C WEB-MAN-0429: 12 183 KB: CPC400 User's Guide, Rev 2.2, Aug. 2005 0600-2900-2000: 230 3.2 MB: Cross Reference for Semiconductor Fuses and Holders for Watlow Power Controllers WEB-MAN-0359: 3 42 KB: DIN-A-MITE Retrofit Guide and User's Manual. DIN-A-MITE® B. The DIN-A-MITE® B is a low-cost, highly compact and versatile solid state electric heat controller. The DIN-A-MITE B capabilities include single-phase and three-phase zero-cross switching up to 40 and 22 amperes, respectively at 600VAC (see rating curve).
WATLOW DIN-A-MITE Style C User's Manual
General Specifications
Operator Interface
• Command signal input and indication light
• Alarm output and indication light
• Current limit indication LED
• Command signal input and indication light
• Alarm output and indication light
• Current limit indication LED
Amperage Rating
See the output rating curve chart on page 5 for all
the natural convection, fan-cooled, and through-
wall mount models.
wall mount models.
Ratings are into a resistive heater load
• Maximum surge current for 16.6 milliseconds, 1,350 A
peak
• Maximum I
2
t for fusing is 9100 A
2
s
• Latching current: 500mA minimum
• Holding current: 200mA minimum
• Fan current: 0.14 A for 24V
• Holding current: 200mA minimum
• Fan current: 0.14 A for 24V
Î
(dc); 0.12 A for 120V
Å
(ac); 0.06A for 240V
Å
(ac)
• Off-state leakage 1mA at 25°C (77°F) maximum
• Power dissipation is 1.2 watts per amp switched
• Power dissipation is 1.2 watts per amp switched
per controlled leg.
• 200KA SCCR type 1 and 2 approved with the
recommended fusing (see page 4)
Line Voltage
• 24 to 48V
• 24 to 48V
Å
(ac) units: 20V
Å
minimum to 53V
Å
maximum
• 120 to 240V
Å
(ac) units: 48V
Å
minimum to 265V
Å
maximum
• 277 to 600V
Å
(ac) units: 85V
Å
minimum to 660V
Å
maximum
Alarms (zero cross models only)
Shorted SCR Alarm Option
• Alarm state when the input command signal is off and
a 10 A or more load current is detected by the current
transformer (two turns required for 5 A or three turns
for 2.5 A).
transformer (two turns required for 5 A or three turns
for 2.5 A).
Open Heater Alarm Option
• Alarm state when the input command signal is on and
the load current detected by the current transformer is
less than the alarm set point. Available with Input
Control Signal option S only.
less than the alarm set point. Available with Input
Control Signal option S only.
Alarm Output
• Energizes on alarm, non-latching
• Triac 24 to 240V
• Triac 24 to 240V
Å
(ac), external supply with a current
rating of 300 mA @ 25°C (77°F), 200mA @ 50°C
(122°F), 100mA @ 80°C (176°F) and a holding current
of 200 µA with a latching current of 5mA typical.
(122°F), 100mA @ 80°C (176°F) and a holding current
of 200 µA with a latching current of 5mA typical.
• Agency Approvals
• CE with proper filter:
• CE with proper filter:
2004/108/EC Electromagnetic Compatibility Directive
EN 61326: Industrial Immunity Class A emissions
Not suitable for Class B environments.
Not suitable for Class B environments.
2006/95/EC Low Voltage Directive
EN 50178 Safety Requirements
Installation category III, Pollution degree 2
Installation category III, Pollution degree 2
Phase angle and phase angle with current limit Input
Control Signal Types (P and L) are not CE approved.
Watlow
• UL
®
50 Type 4X Enclosure and UL ANSI/ISA 12.12.01
Temperature Code T4A
The through-wall heatsink package is suitable for use in
Class I, Division 2 Groups A, B, C and D Hazardous
Locations or unclassified or non-hazardous locations.
Locations or unclassified or non-hazardous locations.
ç
WARNING – EXPLOSION HAZARD
SUBSTITUTION OF ANY COMPONENTS MAY IMPAIR
SUITABILITY FOR CLASS I, DIVISION 2.
SUITABILITY FOR CLASS I, DIVISION 2.
ç
WARNING – EXPLOSION HAZARD
DO NOT DISCONNECT WHILE THE CIRCUIT IS
LIVE OR UNLESS THE AREA IS KNOW TO BE FREE
OF IGNITIBLE CONCENTRATIONS.
LIVE OR UNLESS THE AREA IS KNOW TO BE FREE
OF IGNITIBLE CONCENTRATIONS.
•
UL
®
508 listed and C-UL
®
, File E73741
• Shock and vibration tested to IEC 60068-2-32
• Vibration tested to IEC 60068-2-6
• Vibration tested to IEC 60068-2-6
Input Terminals
• Compression: Will accept 0.2 to 1.5 mm
• Compression: Will accept 0.2 to 1.5 mm
2
(24 to 16
AWG) wire
• Torque to 0.5 Nm (4.4 in-lb) with a 3.5 mm (1/8 in)
blade screwdriver
• Wire strip length 5.5 mm (0.22 in)
Line, Load and Ground Terminals
• Compression: Will accept 2.5 to 25 mm
• Compression: Will accept 2.5 to 25 mm
2
(14 to 3 AWG)
wire
• Torque to 2.7 Nm (24 in-lb) with a 6.4 mm (1/4 in)
blade screwdriver, or a Type 1A #2 Pozi driver.
• Retorque after 48 hours to minimize wire cold flow.
• Retorque line and load terminals every 3 to 6 months.
• Wire strip length 11 mm (7/16 in)
• Retorque line and load terminals every 3 to 6 months.
• Wire strip length 11 mm (7/16 in)
Operating Environment
• See the output rating curve chart on page 5.
• 0 to 90% RH (relative humidity), non-condensing
• Storage temperature: -40 to +85°C (-40 to 185°F)
• Insulation only tested to 3,000 meters
• See the output rating curve chart on page 5.
• 0 to 90% RH (relative humidity), non-condensing
• Storage temperature: -40 to +85°C (-40 to 185°F)
• Insulation only tested to 3,000 meters
DIN Rail Mount
• DIN EN 50022, 35 by 7.5 mm
• Minimum clipping distance: 34.8 mm (1.37 in)
• Maximum clipping distance: 35.3 mm (1.39 in)
• DIN EN 50022, 35 by 7.5 mm
• Minimum clipping distance: 34.8 mm (1.37 in)
• Maximum clipping distance: 35.3 mm (1.39 in)
Back Panel Mount
• Four mounting holes M4 (No. 8) fastener
• Four mounting holes M4 (No. 8) fastener
Through-Wall Mount
• See page 8 for through-wall cutout
• See page 8 for through-wall cutout
NOTE: Mount cooling fins vertically. Cooling fan power
terminals: quick connect, 1/8' push on, 16-14 AWG wire.
Amp part no. 640929-1 or equivalent
terminals: quick connect, 1/8' push on, 16-14 AWG wire.
Amp part no. 640929-1 or equivalent
Weight
• 1.0 to 1.9 kg (2.2 to 4.2 lb) depending upon model
• 1.0 to 1.9 kg (2.2 to 4.2 lb) depending upon model
Specifications are subject to change without notice.